Journal Abbreviation : ‘J. Odor Indoor Environ.’ Frequency : Quarterly Doi Prefix : 10.15250/joie. ISSN : 2288-9167 (Print) / 2288-923X (Online) Year of Launching : 2014 Publisher : Korean Society of Odor Research and Engineering & Korean Society for Indoor Environment Indexed/Tracked/Covered By :
A study on the performance of a SST k-ω model for near field dispersion of odor from rooftop emissions
Ara Kim1,Sang Jin Jeong2*
1Department of Environmental and Energy Engineering, Graduate School, Kyonggi University 2Department of Environmental and Energy Engineering, Kyonggi University
This paper presents the performance of a CFD model for the near field dispersion of odor from rooftop emissions.The FLUENT Shear-Stress Transport (SST hereinafter) k-ω turbulence model was used to simulate odor dispersionfrom a rooftop odor vent. The results were compared with a wind tunnel experiment and the calculated resultsof ASHRAE 2003 and 2007. The FLUENT SST k-ω turbulence model provided good results for makingreasonable predictions about the building rooftop surface normalized dilution. It was found that increasing the ventheight (from 1m to 7m) reduces rooftop surface normalized dilution. ASHRAE 2003 and ASHRAE 2007performance measures are generally not as good as FLUENT SST k-ω turbulence model performance measures,with larger MG (the geometric mean bias, VG (the geometric variance), NMSE (the normalized mean square error),FB (Fractional bias), and smaller FAC2 (the fraction of predictions within a factor of two of observations).