Journal Search Engine
Download PDF Export Citation Korean Bibliography PMC Previewer
ISSN : 1738-4125(Print)
ISSN : 2287-7509(Online)
Journal of Odor and Indoor Environment Vol.3 No.4 pp.407-416
DOI :

칸막이가 설치된 사무실 공간의 냉방효과에 관한 수치해석적 연구

권순박*, 박덕신, 조영민, 박은영
한국철도기술연구원 환경화재연구팀

Numerical Study on the Effects of Air Conditioning in Office of Personal Partitions

Soon-Bark Kwon*, Duck-Shin Park, Young-Min Cho, Eun-Young Park
Environment & Fire Control Research Team, Korea Railroad Research Institute

Abstract

Numerical simulation using computational fluid dynamics (CFD) was performed to calculate the predictedmean vote (PMV) based on velocity and temperature profiles of air in a partitioned office building. Theoffice building (W:14.65 m, D:7.57 m, and H:2.63 m) was divided by partitions of 1.5 m height and sharedby 7 office workers. Each person uses a personal computer and printer on a desk. One stand-type airconditioner was installed in the corner of the room and operated at the variable flow rate of 35 ㎥/min. Inthe case study, we assumed that the initial temperature of the room was 303 K and it was cooled down byoperating air-conditioner. The outside temperature was fixed at 303 K and the heat flux through the windowswas included in the calculation. Heat sources of personal computers, human bodies, fluorescent lamps, andrefrigerator were considered. The temperature and PMV values were also calculated to asses the thermalcomfort of each person by operating time of air conditioner. It was found that the thermal comfort could beimproved by changing the angle of diffuser grill of air conditioner.

A9RD137.pdf800.1KB

Reference