열쾌적성과 국소환기지수를 고려한 에어컨 냉기 최적 토출각도에 대한 수치적 연구

노 광 철, 오 명 도1)*
서울시립대학교 대학원 기계정보공학과, 1)서울시립대학교 기계정보공학과

Numerical Study on the Optimal Discharge Angle of the 4-way Air Conditioner by Thermal Comfort and Local Ventilation Indices

Myung-Do Oh1)*, Kwang-Chul Noh
1)Dept. of Mechanical and Information Engineering, University of Seoul
Dept. of Mechanical and Information Engineering, Graduate School, University of Seoul
Received 20 December 2004, accepted 8 June 2005

Abstract

We performed numerical analyses on the optimal discharge angle of a 4-way cassette air conditioner,which is mounted on the ceiling of the classroom, by using thermal comfort and ventilation indices. Weanalyzed the effective draft temperature, the local mean age and the local mean residual life time withrespect to the variation of the air discharge angle of the air conditioner in all occupied zone. Air diffusionperformance index, local supply effectiveness and local exhaust effectiveness were used to investigate theoptimal value of air discharge angle. From the results, we found out that the optimal discharge angle of theair conditioner is about 40 degrees in the present model.