Journal Search Engine
Download PDF Export Citation Korean Bibliography PMC Previewer
ISSN : 1738-4125(Print)
ISSN : 2287-7509(Online)
Journal of Odor and Indoor Environment Vol.3 No.2 pp.150-157
DOI :

이동통신 기지국 DAC용 에어필터의 성능분석실험

유경훈*, 여국현, 차호진1), 김용우1), 최동규2), 이홍규3)
한국생산기술연구원 에어로졸․오염제어연구실, 1)삼성전자(주) 네트웍사업부
2)엠쏘정보통신. 3)고어코리아

An Experiment on Performance Evaluation of a Direct Ambient Cooling Air Filter for Wireless Telecommunication Base Transceiver Stations

Kyung-Hoon Yoo*, Kuk-Hyun Yeo, Ho-Jin Cha1), Yong-Woo Kim1), Dong-Kyu Choi2), Henry Lee3)
Aerosol and Contamination Control Laboratory, Korea Institute of Industrial Technology(KITECH)
1)Telecommunication System Devision, SAMSUNG Electronics
2)MSO Information and Communication. 3)W.L. GORE & ASSOCIATES KOREA

Abstract

In recent European telecommunication base transceiver stations(BTS), a membrane laminated air filter isreported to replace a heat exchanger in order to cool internal digital units of BTS. The concept of using theair filter is for the direct ambient cooling (DAC) of BTS without heat loss generally found in the heatexchanger type BTS. In the present study, a performance evaluation experiment was conducted toinvestigate the pressure drop characteristics with dust loading and the particle collection efficiency of theair filter for the DAC of BTS. Finally, the long term operation lifetime of the air filter for BTS was suggestedwith a given fan rotation speed.

A9RFB02.pdf1.00MB

Reference